Delta MCS-1800 Specifications Page 47

  • Download
  • Add to my manuals
  • Print
  • Page
    / 66
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 46
NEW!
957
POWER MONITORING & PROTECTION
POWER MONITORING & PROTECTION
16
WE MAKE IT EASY.
kele.com 888-397-5353 USA
ORDERING INFORMATION
MOTORSAVER™ THREE-PHASE VOLTAGE MONITOR
201A
Supply Watts 5W
Frequency 50* or 60 Hz
Transient Protection 2500V for 10 ms
Line Voltage Monitored Three-phase, 190-480
VAC, adjustable
Low Voltage Trip 90% of setpoint
Low Voltage Reset 93% of setpoint
Reset Delay Time after Fault 2 seconds
Reset Delay Time after Power Loss
2 seconds
Trip Delay Time Low Voltage 4 seconds
Trip Delay Time Phase Fault 2 seconds
Trip Delay Time Unbalance 2 seconds
Voltage Unbalance Reset 4.5%
Voltage Unbalance Trip 6%
Dimensions 2.37"W x 1.75"H x 4.25"L
(6.0 x 4.4 x 10.8cm)
Weight 0.56 lb (0.25 kg)
Approvals UL Listed, File #E68520,
CE certified
Warranty 5 years
DESCRIPTION
The MotorSaver 201A Three-Phase Voltage Monitor is
an autoranging plug-in voltage monitor designed to protect
three-phase motors regardless of size. It is used on 190-
480 VAC 50/60 Hz motors to prevent damage caused by
single phasing, low voltage, phase reversal, or voltage
unbalance. To detect harmful power line conditions, the
unique microprocessor-based voltage and phase sensing
circuit constantly monitors the three-phase voltages. When a
harmful condition is detected, the Model 201A MotorSaver's
output relay is deactivated after a fixed trip-delay time period.
The output relay reactivates after power line conditions return
to an acceptable level for a fixed restart delay time. The trip
delay prevents nuisance tripping due to rapidly fluctuating
power line conditions.
FEATURES
Protection of three-phase motors against single
phasing, low voltage, phase reversal, and voltage
unbalance
DIN rail- or surface-mounted socket
UL and ULC listed, CE certified
Bicolor LED indication of normal and fault conditions
Single-phase condition detection regardless of
regenerated voltages
OL
OL
OL
OL
Motor
L1
L1
L2
L3
L2 L3
M
Start
M
M
M
M
Stop
Hand
Auto Pilot
Off
Control
Voltage
240 VAC max
201A
2
81
435
WIRING
MODEL DESCRIPTION
201A MotorSaver three-phase voltage monitor
OT08PC Socket, 600 VAC, DIN rail or surface mount
SPECIFICATIONS
Shown de-energized
Model 201A
* 50 Hz will increase all delay times by 20%.