POWER MONITORING & PROTECTION
POWER MONITORING & PROTECTION
16
WE MAKE IT EASY.
kele.com 888-397-5353 USA
ORDERING INFORMATION
MOTORSAVER™ THREE-PHASE VOLTAGE MONITOR
460
Supply Watts 6W maximum
Frequency 50*/60 Hz
Humidity 10-95% RH, non-condensing
Contact Rating SPDT, pilot duty 480 VA @ 240 VAC
General-purpose 10A @ 240 VAC
Transient Protection IEC 1000-4-5, ANSI/IEEE C62.41,
UL508
Line Voltage Monitored 190-480
Low Voltage Trip 90% of setpoint (±1%)
Low Voltage Reset 93% of setpoint (±1%)
Reset Delay Time
after Fault 1-500 second adjustable
Reset Delay Time
after Power Loss 1-500 second adjustable
Trip Delay Time
High Voltage 1-30 second adjustable
Trip Delay Time
Low Voltage 1-30 second adjustable
Trip Delay Time
Phase Fault 1 second fixed
Trip Delay Time
Unbalance 1-30 second adjustable
Voltage Unbalance Reset
Trip setting minus 1% (5-8%) Trip
setting minus 0.5% (2-4%)
Voltage Unbalance Trip 2% to 8%, adjustable
Operating Temperature -4° to 158°F (-20° to 70°C)
Dimensions 3.5"H x 2.1"W x 2.4"D
(8.9 x 5.3 x 6.1 cm)
Weight 0.9 lb (0.4 kg)
Approvals UL and cUL listed, File #E68520, CE
Warranty 5 years
DESCRIPTION
The MotorSaverModel 460 microcontroller-based
voltage and phase sensing circuit constantly monitors the
three phase voltage to detect harmful power line conditions.
When a harmful condition is detected, the Model 460 output
relay is deactivated after an adjustable trip delay time. The
output relay reactivates after power line conditions return to
an acceptable level for an adjustable restart delay time. If
equipped with the manual reset option, an external normally
open momentary reset switch must be closed to reactivate
the output relay. The trip and restart delays prevent nuisance
tripping due to rapidly fluctuating power line conditions.
The Model 460 automatically senses whether it is connected
to a 190-240V 60 Hz system, a 440-480V 60 Hz system, or
a 380-416V 50 Hz system. An adjustment is provided to set
the nominal line voltage from 190-240 or 380-480 VAC. Other
adjustments include a 1-30 second trip delay, a 1-500 second
restart delay, and a 2% to 8% voltage-unbalance trip point
adjustment.
FEATURES
Protection of three-phase motors from loss of any
phase, low-voltage, phase reversal, voltage unbalance,
and high voltage
Adjustable restart delay
Adjustable trip delay
Adjustable voltage unbalance trip point
Optional manual reset
Diagnostic LEDs for indication of trip status
Single-phase condition detection regardless of
regenerated voltages
Surface or DIN rail mounting
Control Power
24-240 VAC
External
Normally Open
Momentary Manual
Reset Switch
(customer
supplied)
Shown de-energized
Model 460
Input
Power
Motor
OL
OL
OL
OL
L1
L1
L2
L3
L2 L3
4
5
6
12
3
Auto
Pilot Contact
Manual Reset
on 460-MR only
Off
Manual
Stop
Start
M
M
Magnetic
Contactor
WIRING
SPECIFICATIONS
460
* 50 Hz will increase all delay times by 20%.
MODEL DESCRIPTION
460 Three-phase voltage monitor, 190-480 VAC
460-MR Three-phase voltage monitor, 190-480 VAC with manual reset
460-575 Three-phase voltage monitor, 190-480 VAC, 1-30 second trip delay, 1-500 second restart delay, 2-8% voltage unbalance trip point