Delta MCS-1800 Specifications Page 59

  • Download
  • Add to my manuals
  • Print
  • Page
    / 66
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 58
NEW!
969
POWER MONITORING & PROTECTION
POWER MONITORING & PROTECTION
16
WE MAKE IT EASY.
kele.com 888-397-5353 USA
ORDERING INFORMATION
LIGHTNING ARRESTER
392-SVSR2
Impulse Breakdown
@100/V/μsec 300-750V
DC Holder 150 VDC extinguishing in
less than 150 ms
Insulation Resistance
(initial) <100 M
Capacitance 5 pF
Impulse Life Specification Rated Heavy-Duty
80% survival to 400
surges of 500A
AC Discharge
Current 65A, 11 cycle, 60 Hz
End-Of-Life Limits
Insulation Resistance <1 M
DC Breakdown Voltage <180V
Impulse Breakdown Voltage <900V
Vented (back-up)
DC Breakdown Voltage <1600V (100-200 avg)
Max Single
Impulse Discharge Current 10 kA, 8 x 20 µsec surge
Dimensions 3.5"H x 3.75"W x 2.5"D
(8.9 x 9.5 x 6.4 cm)
Weight 0.85 lb (0.39 kg)
Approvals UL listed File #E2332
DESCRIPTION
The Model 392-SVSR2 is a two-pair gas tube lightning
arrester in a plastic outdoor enclosure. It protects the
communication lines that run between buildings against high
voltage transients caused by motors, transmitters, lightning,
etc.
Transients can be harmful and even capable of destroying
building automation systems. It is recommended that
the Model 392-SVSR2 be used at all points where
communication cables exit or enter a building. To protect
low voltage communication inputs on Building Automation
Systems, this device should be used in conjunction with an
appropriate voltage level surge protector such as a Model
DTK-2LVLP.
If a shield is used, then
ground at one end only.
Use #6 AWG solid wire to
copper clad steel ground
rod (min. 8'/2.4m deep)
through shortest path with
no sharp bends.
(white)
(white)
(orange)
(red)
(red)
(blue)
(blue)
(orange)
392-SVSR2
Notes: To protect low-voltage communication circuits, this device
should be used in conjunction with an appropriate voltage
level surge protector such as the Model DTK-2LVLP.
When applying surge protectors, use of the protection
zone concept is recommended.
WIRING
SPECIFICATIONS
392-SVSR2
MODEL DESCRIPTION
392-SVSR2 Lightning arrester