Delta MCS-1800 Specifications Page 63

  • Download
  • Add to my manuals
  • Print
  • Page
    / 66
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 62
NEW!
973
POWER MONITORING & PROTECTION
POWER MONITORING & PROTECTION
16
WE MAKE IT EASY.
kele.com 888-397-5353 USA
DETERMINING BURDEN FOR CURRENT TRANSFORMERS
You can see from the above example that if the total burden (wire plus device) is only 2.5 VA, the accuracy of the reading will be
±0.6%. If a higher burden (up to 12.5 VA) is used, the accuracy will be ±1.2%.
For lower-line currents, the accuracy at 10% of the CT rating (120A through a 1200:5 CT) is double the published value. On the
above example, at 2.5 VA burden, the accuracy would be ±1.2%. At a 12.5 VA burden, the accuracy would be ±2.4%.
BURDEN CALCULATION
STEP 1: Determine the burden of the connected device in VA or ohms impedance. This should be on the device data sheet.
STEP 2: Add impedance of the secondary wire run. Measure the length of the wire run between current transformer and the
burden (e.g., meter, relay, transducer, etc.). Refer to Nomogram No. 2 and determine the resistance, in ohms, of the
wires that connect the secondary of the current transformer to the devices. The Nomogram makes allowances for
the return wire. Add this resistance from Nomogram No. 2 to the impedance of the connected burdens. Nomogram
No.1 will help convert ohms to VA.
STEP 3: Make sure the total burden does not exceed the specified limits for the chosen CT.
If a current transformer (CT) reads low, then the secondary is probably overloaded. Burden is the load which may be imposed
on a transformer secondary by cables and connected devices without causing an error greater than the stated accuracy
classification. Lower burden and proper sizing can improve the accuracy of the CT. It is a good idea to check your CT burden if
the CT primary rating is under 200A.
Burden is expressed in ohms impedance or volt-amperes for current transformers. The standard burden limits are defined by
ANSI C57.13.
CURRENT TRANSFORMERS
CTs carry an ANSI burden designation "B" followed by the ohms limit (e.g., B0.1). Below is a typical CT specification in our
catalog:
Allowable burden in ohms (0.5 max)
Allowable burden in volt-amperes (12.5 VA max)
Accuracy at burden above (e.g., ±1.2%)
CT primary to secondary ratio
Model # Current ANSI Meter Class at 60 Hz
Ratio B0.1 B0.2 B0.5
2.5 VA 5 VA 12.5 VA
600T-122 1200:5 0.6 1.2 1.2
Line
CT
Devices
(Meter, Relay,
Transducer, etc.)
RD
Wire = Rw
Burden = RW + RD
March 2014
Page view 62
1 2 ... 58 59 60 61 62 63 64 65 66

Comments to this Manuals

No comments