36 & 54kW 3-Phase panel mount, heater controller
RE-PR3-E-36/54
Data Sheet Ref: 90501161
Issue: 5.2
International Tel: +44 1732 861225
UK Sales Tel: 0845 345 7253
International Fax: +44 1732 861226
UK Sales Fax: 0845 345 7353
www.sontay.com
Whilst every effort has been made to ensure the accuracy of this specification, Sontay cannot accept responsibility for damage, injury, loss or
expense resulting from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.
90800066 Issue 1
Technical Overview
Features
Specification Product Codes
The RE-PR3-E-xx are a range Thyristor control assemblies
that provides full seamless control of 3-phase resistive loads
of up to 36 & 54kW, using two thirds control technique. They
are controlled by a 0-5Vdc, 0-10Vdc signal or manual 5K
pot.
This burst fire control assemblies use fast pulse, zero volt,
switching technology to minimise flicker and eliminate RFI
problems.
They also incorporate a temperature trip, automatic reset,
alarm output, LED ’output on’ indication and heatsink.
Applications include electric heater batteries and dust heat-
ers.
0-5Vdc, 0-10Vdc or manual 5K pot control input
Over temperature protection with auto reset
No additional heatsinks required
Input signal 0-5Vdc, 0-10Vdc or manual 5K pot
Supply (control) 24Vac/dc ±10% (by dipswitch)
Supply (load) 3-Phase 400V RMS ±10% 50/60Hz
Power /current ratings:
RE-PR3-E-36 36kW (50A per phase)
RE-PR3-E-54 54kW (75A per phase)
Fusing:
RE-PR3-E-36 56A H/S semiconductor (integral)
RE-PR3-E-54 80A H/S semiconductor (integral)
Terminal connections:
Auxiliary alarm Rising cage for 2.5mm² cable max.
Control Rising cage for 2.5mm² cable max.
Power:
RE-PR3-E-36 Rising cage for 10mm² cable max.
RE-PR3-E-54 Rising cage for 16mm² cable max.
Terminal torque settings:
RE-PR3-E-36 2Nm (power terminals only)
RE-PR3-E-54 2.5Nm (power terminals only)
Over temperature:
Trip in temp. @ 90°C ±1°C
Trip out temp. @ 85°C ±1°C
Fault condition Relay rated at 230Vac @ 8A
Fault status:
Phase loss LED flashes in 1.5 sec. pulse bursts
Sensor loss LED flashes in 0.5 sec. pulse bursts
Ambient temperature 65°C (maximum operational)
Dimensions (L, W, H):
RE-PR3-E-36 205 x 155 x 120mm
RE-PR3-E-54 250 x 155 x 120mm
Conformity CE Marked
Country of origin UK
RE-PR3-E-36
Panel mount 3-phase 36kW electric heater controller
RE-PR3-E-54
Panel mount 3-phase 54kW electric heater controller
Page view 0
1 2 3 4

Summary of Contents

Page 1 - 90800066 Issue 1

Page 1 36 & 54kW 3-Phase panel mount, heater controller RE-PR3-E-36/54 Data Sheet Ref: 90501161 Issue: 5.2 International Tel: +44 1732 861225 UK

Page 2

Page 2 36 & 54kW 3-Phase panel mount, heater controller RE-PR3-E-36/54 Data Sheet Ref: 90501161 Issue: 5.2 International Tel: +44 1732 861225 UK

Page 3

Page 3 36 & 54kW 3-Phase panel mount, heater controller RE-PR3-E-36/54 Data Sheet Ref: 90501161 Issue: 5.2 International Tel: +44 1732 861225 UK

Page 4

Page 4 36 & 54kW 3-Phase panel mount, heater controller RE-PR3-E-36/54 Data Sheet Ref: 90501161 Issue: 5.2 International Tel: +44 1732 861225 UK

Comments to this Manuals

No comments