Delta DVP-ES2 User Manual Page 111

  • Download
  • Add to my manuals
  • Print
  • Page
    / 702
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 110
2. Programming Concepts
accessible and the user can specify the starting register for storing the read/written data.
f)
to the
g) Mast
e
9.
a) Auto
desc 1350 or M1351 is OFF.
accessing all Slaves. When PLC
n baud rate is higher than 1200 bps. When baud
lid when data length to be accessed is set to 0.
. PLC will take the upper / lower bound value as the
set value if the specified value exceeds the availanle range.
D1399 has to be set up before enabling PLC LINK. Setting up this register during PLC
e effect.
nd
For example, if the register for storing the read/written data on Slave ID1 is specified as
D1480 = K500, D1496 = K800, access data length D1434 = K50, D1450 = K50, registers of
Master PLC D500~D549 will store the data read from Slave ID1, and the data stored in
D800~D849 will be written into Slave ID1.
Master PLC conducts reading before writing. Both reading and writing is executed according
range specified by user.
er PLC accesses slave PLCs in order, i.e. data access moves to next slave only when
acc ss on previous slave is completed.
Auto mode and Manual mode:
mode (M1351): when M1351 = ON, Master PLC will access slave PLCs as the operation
ribed above, and stop the polling till M
b) Manual mode (M1352): When manual mode is selected, times of polling cycle in D1431 has
to be set up. A full polling cycle refers to the completion of
LINK is enabled, D1432 starts to store the times of polling. When D1431 = D1432, PLC LINK
stops and M1352 is reset. When M1352 is set ON again, PLC will start the polling according
to times set in D1431 automatically.
c) Note:
Auto mode M1351 and manual mode M1352 cannot be enabled at the same time. If
M1351 is enabled after M1352 is ON, PLC LINK will stop and M1350 will be reset.
Communication timeout setting can be modified by D1129 with available range 200
D1129 3000. PLC will take the upper / lower bound value as the set value if the
specified value is out of the available range. D1129 has to be set up before M1350 = ON.
PLC LINK function is only valid whe
rate is less than 9600 bps, please set communication time-out to more than 1 second.
The communication is inva
Access on 32-bit high speed counters (C200~C255) is not supported.
Available range for D1399: 1 ~ 230
LINK execution will not tak
Advantage of using D1399 (Designating the ID of starting Slave):
In old version PLC LINK, PLC detects Slaves from ID1 to ID16. Therefore, when PLC
LINK is applied in multi-layer networks, e.g. 3 layers of networks, the Slave ID of 2 and
3
rd
layer will be repeated. When Slave ID is repeated, i.e. the same as Master ID, the
Slave will be passed. In this case, only 15 Slaves can be connected in 3
rd
layer. To
solve this problem, D1399 can be applied for increasing the connectable Slaves in multi-
layer network structure.
2-79
Page view 110
1 2 ... 106 107 108 109 110 111 112 113 114 115 116 ... 701 702

Comments to this Manuals

No comments