Delta DVP-ES2 User Manual Page 125

  • Download
  • Add to my manuals
  • Print
  • Page
    / 702
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 124
3. Instruction Set
3-9
between MC/MCR will operate as the following table.
Instruction type Explanation
General purpose timer Present value = 0, Coil is OFF, No action on associated contact
Subroutine timer Present value = 0, Coil is OFF, No action on associated contact
Accumulative timer Coil is OFF, present value and contact status remains
Counter Coil is OFF, present value and contact status remains
Coils driven by OUT instruction All OFF
Devices driven by SET/RST
instructions
Stay intact
Application instructions
All disabled.
The FOR-NEXT nested loop will still execute back and forth for N
times. Instructions between FOR-NEXT will act as other
instructions between MC and MCR.
Note: MC-MCR master-control instruction supports max 8 layers of nest levels. Please use the
instructions in order from N0~ N7.
Program example:
Ladder diagram: Instruction: Operation:
LD X0 Load NO contact X0
MC N0 Enable N0 nest level
LD X1 Load NO contact X1
OUT Y0 Drive coil Y1
:
LD X2 Load NO contact X2
MC N1 Enable N1 nest level
LD X3 Load NO contact X3
OUT Y1 Drive coil Y1
:
MCR N1 Reset N1 nest level
:
MCR N0 Reset N0 nest level
:
LD X10 Load NO contact X10
MC N0 Enable N0 nest level
LD X11 Load NO contact X11
OUT Y10 Drive coil Y10
:
X0
Y0
MC N0
X1
X2
Y1
MC N1
X3
MCR N1
MCR N0
X10
MC N0
Y10
X11
MCR N0
MCR N0 Reset N0 nest level