DVP-ES2/SA2/SS2/SA2/SX2/SE Operation Manual - Programming
3-50
3. Interrupt subroutines must be placed after the FEND instruction.
4. Other interrupts are not allowed during execution of a current interrupt routine.
5. When many interruptions occur, the priority is given to the firstly executed interruption. If
several interruptions occur at the same time, the priority is given to the interruption with the
smaller pointer No.
6. Any interrupt request occurring between DI and EI instructions will not be executed
immediately. The interrupt will be memorized and executed when the next EI occurs.
7. When using the interruption pointer, DO NOT repeatedly use the high-speed counter driven
by the same X input contact.
8. When immediate I/O is required during the interruption, write REF instruction in the program
to update the status of I/O
Points to note:
Interrupt pointers (I):
a) External interrupts: 8 points including (I000/I001, X0), (I100/I101, X1), (I200/I201, X2),
(I300/I301, X3), (I400/I401, X4), (I500/I501, X5), (I600/I601, X6) and (I700/I701, X7) (00
designates interruption in falling-edge, 01 designates interruption in rising-edge)
b) Timer interrupts: 2 points including I605~I699 and I705~I799 (Timer resolution = 1ms)
c) High-speed counter interrupts: 8 points including I010, I020, I030, I040, I050, I060, I070, and
I080. (used with API 53 DHSCS instruction to generate interrupt signals)
d) Communication interrupts: 3 points including I140, I150 and I160
e) Associated flags:
Flag Function
M1050 Disable external interruption I000 / I001
M1051 Disable external interruption I100 / I101
M1052 Disable external interruption I200 / I201
M1053 Disable external interruption I300 / I301
M1054 Disable external interruption I400 / I401
M1055 Disable external interruption I500 / I501, I600 / I601, I700 / I701
M1056 Disable timer interrupts I605~I699
M1057 Disable timer interrupts I705~I799
M1059 Disable high-speed counter interruptions I010~I080
M1280 I000/I001 Reverse interrupt trigger pulse direction (Rising/Falling)
M1284 I400/I401 Reverse interrupt trigger pulse direction (Rising/Falling)
M1286 I600/I601 Reverse interrupt trigger pulse direction (Rising/Falling)
Note: Default setting of I000(X0) is falling-edge triggered. When M1280=ON and EI is enabled,
PLC will reverse X0 as rising-edge triggered. To reset X0 as falling-edge, reset M1280 first and