3. Instruction Set
3-63
API Mnemonic Operands Function
12
D MOV P
Move
Controllers
ES2/EX2 SS2
SA2
SE
SX2
Bit Devices Word devices Program Steps Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S
* ** * * * * * ***
D
* * * * * ***
MOV, MOVP: 5 steps
DMOV, DMOVP: 9 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S: Source of data D: Destination of data
Explanations:
1. When this instruction is executed, the content of S will be moved directly to D. When this
instruction is not executed, the content of D remains unchanged
2. If operand S and D use index register F, only 16-bit instruction is applicable
Program example:
1. MOV will move a 16-bit value from the source location to the destination.
a) When X0 = OFF, the content of D0 remains unchanged. If X0 = ON, the data in K10 is
moved to D0.
b) When X1 = OFF, the content of D10 remains unchanged. If X1 = ON, the data of T0 is
moved to D10 data register.
2. DMOV will move a 32-bit value from the source location to the destination.
a) When X2 = OFF, the content of (D31, D30) and (D41, D40) remain unchanged.
b) When X2 = ON, the data of (D21, D20) is moved to (D31, D30) data register. Meanwhile, the