API Mnemonic Operands Function
13
SMOV P
Shift
Move
Controllers
ES2/EX2 SS2
SA2
SE
SX2
Bit Devices Word devices Program Steps Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S * * * * * * ***
m
1
* *
m
2
* *
D * * * * * ***
n * *
SMOV, SMOVP: 11 step
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S: Source device m
1
: Start digit to be moved from source device m
2
: Number of digits to be
moved D: Destination device n: Start digit of the destination device for the moved digits
Explanation:
1. This instruction is able to re-allocate or combine data.
When the instruction is executed, m
2
digits of contents starting from digit m
1
(from high digit to low digit) of S will be sent to m
2
digits starting from digit n (from high digit to low digit) of D.
2. M1168 is used for designating SMOV working mode. When M1168 = ON, the instruction is in
BIN mode. When M1168 = OFF, the instruction is in BCD mode.
Points to note:
1. The range of m
1
: 1 – 4
2. The range of m
2
: 1 – m
1
3. The range of n: m
2
– 4