3. Instruction Set
3-125
¾ Table of settings for the high-speed interrupts of the software counters and software
comparators:
Counter C232 C233 C234 C235 C236 C237
DHSCS High-speed
interrupt
I010 I050 I070 I010 I020 I030
High-speed comparator
Set
C232~C242 share 6 software comparators
Counter C238 C239 C240 C241 C242
DHSCS High-speed
interrupt
I040 I050 I060 I070 I080
High-speed comparator
Set
C232~C242 share 6 software comparators
¾ DVP-SS2/SA2/SE does not support the software high speed counter C232.
¾ C253 and C254 is DVP/SE are software high speed counters. The high-speed interrupt
is I030.
¾ Block diagram of software counters and comparators:
Software
Counter 1
Software
counter
2
Software
counter
8
Count value
Software
comparator
x 6
1
2
6
Set / reset
Set / reset
Set / reset
6. Explanations on hardware comparators
DHSCS/DHSCR instruction:
¾ There are 2 groups of hardware comparators provided respectively for 2 groups of
hardware counters (A group and B group), and each group shares 4 comparators with
individual Compare Set/Reset function.
¾ When programming DHSCS and DHSCR instructions, the total of Set/Reset
comparisons for both instructions can not be more than 4, otherwise syntax check error
will occur.
¾ Each high-speed counter interrupt occupies an associated hardware comparator,
consequently the interrupt number can not be repeated. Also, I010~I040 can only be
applied for group A comparators and I050~I080 for group B.