3. Instruction Set
3-183
API Mnemonic Operands Function
70
D TKY
Ten key input
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices Word devices Program Steps Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S * * * *
D
1
* * * * * ***
D
2
** *
TKY: 7 steps
DTKY: 13 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S: Start device for key input (occupies 10 consecutive devices) D
1
: Device for storing keyed-in
value D
2
: Output signal (occupies 11 consecutive devices)
Explanations:
157. This instruction designates 10 external input points (corresponding to decimal numbers 0 ~ 9)
starting from S, connecting to 10 keys respectively. Input point started from S triggers
associated device in D
2
and D
2
maps to a decimal value, a 4-digit decimal value 0~9,999
(16-bit instruction) or an 8-digit value 0~99,999,999 (32-bit instruction). The decimal value is
stored in D
1.
158. There is no limitation on the times of using this instruction in the program, however only one
instruction is allowed to be executed at the same time.
Program Example:
159. Connect the 10 input points starting from X30 to the 10 keys (0 ~ 9). When X20 = ON, the
instruction will be executed and the key-in values will be stored in D0 in BIN form. The key
status will be stored in M10 ~ M19.
X20
TKY X30 D0 M10
ELC
0 1 32 4 5 6 7 8 9
X33X32X31X30S/S X36X35X34
X40
X37 X41+24V24G
Page view 298