DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming
Specifications
I602~I699, I702~I799, 2 points (Timer resolution =
1ms)
Timer interrupt
High-speed
I010, I020, I030, I040, I050, I060, I070, I080,8
points
counter interrupt
Communication
I140(COM1), I150(COM2), I160(COM3), 3 points,
(*3)
interrupt
K-32,768 ~ K32,767 (16-bit operation),
K Decimal K-2,147,483,648 ~ K2,147,483,647 (32-bit
operation)
Constant
H0000 ~ HFFFF (16-bit operation),
H Hexadecimal
H00000000 ~HFFFFFFFF (32-bit operation)
COM1: built-in RS-232 ((Master/Slave)
COM2: built-in RS-485 (Master/Slave)
Serial ports
COM3: built-in RS-485 (Master/Slave)
COM1 is typically the programming port.
Real Time Clock Year, Month, Day, Week, Hours, Minutes, Seconds
Special I/O Modules Up to 8 special I/O modules can be connected
Notes:
1. Non-latched area cannot be modified
2. Latched area cannot be modified
3. COM1: built-in RS232 port. COM2: built-in RS485 port. COM3: built-in RS485 port.
4. When input points(X) are expanded to 256 points, only 16 output points(Y) are applicable. Also,
when ouput points(Y) are expanded to 256 points, only 16 input points(X) are applicable.
5. This area is applicable only when the ES2/EX2 MPU is connected with special I/O modules.
Every special I/O module occupies 10 points.
2-4