Delta DVP-ES2 User Manual Page 419

  • Download
  • Add to my manuals
  • Print
  • Page
    / 702
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 418
3. Instruction Set
3-303
API Mnemonic Operands Function
120
D EADD P
Floating point addition
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices Word devices Program Steps Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S
1
* * *
S
2
* * *
D *
DEADD, DEADDP: 13
steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S
1
: Augend S
2
: Addend D: Addition result
Explanations:
1. S
1
+ S
2
= D. The floating point value in S
1
and S
2
are added and the result is stored in D.
2. If the source operand S
1
or S
2
is specified as constant K or H, the constant will automatically
be converted to binary floating point value for the addition operation.
3. S
1
and S
2
can designate the same register. In this case, if the instruction is specified as
“continuous execution instruction” (generally DEADDP instruction) and the drive contact is ON,
the register will be added once in every scan.
4. Flags: M1020 (Zero flag), M1021 (Borrow flag) and M1022 (Carry flag)
If absolute value of the result exceeds max. floating point value, carry flag M1022 = ON.
If absolute value of the result is less than min. floating point value, borrow flag M1021 = ON.
If the conversion result is 0, zero flag M1020 = ON.
Program Example 1:
When X0 = ON, add the binary floating point value (D1, D0) with binary floating point value (D3, D2)
and store the result in (D11, D10).
D0DEADD
X0
D2 D10
Program Example 2:
When X2 = ON, add the binary floating point value of (D11, D10) with K1234 (automatically
converted to binary floating point value) and store the result in (D21, D20).
D10DEADD
X2
K1234 D20
Page view 418
1 2 ... 414 415 416 417 418 419 420 421 422 423 424 ... 701 702

Comments to this Manuals

No comments