DVP-ES2/EX2/SS2/SA2/SX2 Operation Manual - Programming
3-406
API Mnemonic Operands Function
179
D WSUM P
Sum of multiple
devices
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices Word devices Program Steps Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S
* * *
n
* * *
D * * *
WSUM, WSUMP: 7 steps
DWSUM, DWSUMP: 13
steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S: Source device n: Data length to be summed up D: Device for storing the result
Explanations:
1. WSUM instruction sums up n devices starting from S and store the result in D.
2. If the specified source devices S are out of valid range, only the devices in valid range will be
processed.
3. Valid range for n: 1~64. If the specified n value is out of the available range (1~64), PLC will
take the upper (64) or lower (1) bound value as the set value.
Program example:
When X10 = ON, 3 consecutive devices (n = 3) from D0 will be summed up and the result will be
stored in D10
X10
WSUM D0 D10
K3
D0
D1
D2
D10
K338
K100
K113
K125
(D0+D1+D2)
D10
Result: