DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming
2-26
Special
M
Function
ES2
EX2
SS2 SA2 SX2
OFF
Ø
ON
STOP
Ø
RUN
RUN
Ø
STOP
Attrib.
Latch
-ed
Default
M1346*
Output clear signals when ZRN is
completed
OFF
- - R/W NO
OFF
M1347
Auto-reset Y0 when high speed pulse
output is completed
OFF
- - R/W NO
OFF
M1348
Auto-reset Y1 when high speed pulse
output is completed
OFF
- - R/W NO
OFF
M1350*
Enable PLC LINK
Off - OFF R/W NO OFF
M1351*
Enable auto mode on PLC LINK
OFF - - R/W NO OFF
M1352*
Enable manual mode on PLC LINK
OFF - - R/W NO OFF
M1353*
Enable access up to 50 words through
PLC LINK (If M1353 is ON,
D1480~D1511 are latched devices.)
OFF - - R/W YES OFF
M1354*
Enable simultaneous data read/write in a
polling of PLC LINK
OFF - - R/W NO OFF
M1355*
Select Slave linking mode in PLC LINK
(ON: manual; OFF: auto-detection)
- - - R/W YES OFF
M1356*
Enable station number selection function.
When both M1353 and M1356 are ON,
the user can specify the station number
in D1900~D1931
○╳○
- - - R/W YES OFF
M1360*
Slave ID#1 status on PLC LINK network
- - - R/W YES OFF
M1361*
Slave ID#2 status on PLC LINK network
- - - R/W YES OFF
M1362*
Slave ID#3 status on PLC LINK network
- - - R/W YES OFF
M1363*
Slave ID#4 status on PLC LINK network
- - - R/W YES OFF
M1364*
Slave ID#5 status on PLC LINK network
- - - R/W YES OFF
M1365*
Slave ID#6 status on PLC LINK network
- - - R/W YES OFF
M1366*
Slave ID#7 status on PLC LINK network
- - - R/W YES OFF
M1367*
Slave ID#8 status on PLC LINK network
- - - R/W YES OFF
M1368*
Slave ID#9 status on PLC LINK network
- - - R/W YES OFF
M1369*
Slave ID#10 status on PLC LINK network
- - - R/W YES OFF
M1370*
Slave ID#11 status on PLC LINK network
- - - R/W YES OFF
M1371*
Slave ID#12 status on PLC LINK network
- - - R/W YES OFF
M1372*
Slave ID#13 status on PLC LINK network
- - - R/W YES OFF
M1373*
Slave ID#14 status on PLC LINK network
- - - R/W YES OFF
M1374*
Slave ID#15 status on PLC LINK network
- - - R/W YES OFF
M1375*
Slave ID#16 status on PLC LINK network
- - - R/W YES OFF
M1376*
Indicate Slave ID#1 data interchange
status on PLC LINK
OFF - - R NO OFF
M1377*
Indicate Slave ID#2 data interchange
status on PLC LINK
OFF - - R NO OFF
Page view 57