Page view 591
DVP-ES2/SX2/SS2/SA2/SX2/SE Operation Manual – Programming
3-476
API Mnemonic Operands Function
268
D
BRST
Reset Specified Bit of a Word
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices Word devices Program Steps
Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
D
* * * * * *
n * * * * * * * * ***
BRST: 5 steps
DBRST: 9 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
D: Destination device to be reset n: Device specifying the bit to be reset
Explanations:
1. For ES2/EX2 models, only V1.20 or above supports the function.
2. Available range for the value in operand n: K0~K15 for 16-bit instruction; K0~K31 for 32-bit
instruction.
3. When BRST instruction executes, the output device specified by operand n will be reset
(OFF).
Program Example:
X0
BRST K4Y0 D0
Instruction: Operation:
LD X0 Load NO contact X0
BRST
K4Y0 D0
When D0 = k1,
Y1 is OFF
When D0 = k2,
Y2 = OFF