3. Instruction Set
3-477
API Mnemonic Operands Function
269
D
BLD
Load NO Contact by Specified Bit
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices Word devices Program Steps
Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S
* * * * * *
n * * * * * * * * ***
BLD: 5 steps
DBLD: 9 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S: Reference source device n: Reference bit
Explanations:
1. For ES2/EX2 models, only V1.20 or above supports the function.
2. Available range for the value in operand n: K0~K15 for 16-bit instruction; K0~K31 for 32-bit
instruction.
3. BLD instruction is used to load NO contact whose contact state is defined by the reference bit
n in reference device D, i.e. if the bit specified by n is ON, the NO contact will be ON, and vice
versa.
Program Example:
BLD D0 K3 Y0
Instruction: Operation:
BLD D0 K3 Load NO contact with bit
status of bit3 in D0
OUT Y0 Drive coil Y0
Page view 592