DVP-ES2/SX2/SS2/SA2/SX2/SE Operation Manual – Programming
3-484
API Mnemonic Operands Function
281~
286
FAND
Floating Point Contact Type
Comparison AND
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices Word devices Program Steps
Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S
1
* * *
S
2
* * *
FAND: 9 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S
1
: Source device 1 S
2
: Source device 2
Explanations:
1. This instruction compares the content in S
1
and S
2
. Take “FAND =” for example, if the result is
“=”, the continuity of the instruction is enabled. If the result is “”, the continuity of the
instruction is disabled.
2. The user can specify the floating point value directly into operands S
1
and S
2
(e.g. F1.2) or
store the floating point value in D registers for further operation.
3. FAND instruction is used for serial connection with contacts.
API No.
32-bit instruction Continuity condition Discontinuity condition
281
FAND S
1
S
2
S
1
S
2
282
FAND S
1
S
2
S
1
S
2
283
FAND S
1
S
2
S
1
S
2
284
FAND<> S
1
S
2
S
1
S
2
285
FAND<= S
1
S
2
S
1
S
2
286
FAND>= S
1
S
2
S
1
S
2
Program Example:
When X1 is OFF and the content in D100(D101) is not equal to F1.2, Y21 = ON and latched.
FAND<>
F1.2 D0
SET Y21
X1
Page view 599