4. Communications
Field Name ASCII
Force Data Lo 00
Error Check (LRC) F6
END 1 0D (Hex)
END 0 0A (Hex)
4.5.5 Command Code: 06, Set content of single register
Example: Set content of register T0: 12 34 (Hex)
PCPLC “: 01 06 06 00 12 34 AD CR LF”
Sent message:
Field Name ASCII
STX :
Slave Address 01
Command code 06
Register Address Hi 06
Register Address Lo 00
Preset Data Hi 12
Preset Data Lo 34
Error Check (LRC) AD
END 1 0D (Hex)
END 0 0A (Hex)
PLCPC “: 01 06 06 00 12 34 AD CR LF”
Feedback message:
Field Name ASCII
STX :
Slave Address 01
Command code 06
Register T0 Address Hi 06
Register T0 Address Lo 00
Preset Data Hi 12
Preset Data Lo 34
Error Check (LRC) AD
END 1 0D (Hex)
END 0 0A (Hex)
4-17
Page view 618
1 2 ... 614 615 616 617 618 619 620 621 622 623 624 ... 701 702