DVP-ES2EX2/SS2/SA2/SX2/SE Operation Manual - Programming
6. Restrictions on diverging sequence: Please refer to section 5.5 for examples
a) Max. 8 step points could be used for single divergence sequence.
b) Max. 16 step points could be used for the convergence of multiple diverted sequences.
c) Users can assign a step in the sequence to jump to any step in another sequence.
7. Reset step points and disable outputs
a) Use the ZRST instruction to reset (turn off) a specified step sequence..
b) Set ON the flag M1034 to disable Y outputs.
8. Latched step:
The ON/OFF status of the latched step will be memorized when the power of the PLC is
switched off. When the PLC is powered up again, PLC will resume the status before power-off
and executes from the interrupted point. Please be aware of the area for the latched steps.
9. Special auxiliary relays and special registers: For more details please refer to 5.6 IST
Instruction.
Device Description
M1040 Disabling step transition.
M1041 Step transition start. Flag for IST instruction.
M1042 Enabling pulse operation. Flag for IST instruction.
M1043 Zero return completed. Flag for IST instruction.
M1044 Zero point condition. Flag for IST instruction.
M1045 Disabling “all output reset” function. Flag for IST instruction.
M1046 Indicating STL status. M1046 = ON when any step is ON
M1047 Enabling STL monitoring
D1040 No. of the 1st step point which is ON.
D1041 No. of the 2nd step point which is ON
D1042 No. of the 3rd step point which is ON.
D1043 No. of the 4th step point which is ON
D1044 No. of the 5th step point which is ON.
D1045 No. of the 6th step point which is ON
D1046 No. of the 7th step point which is ON.
D1047 No. of the 8th step point which is ON
5-10