Delta DVP-ES2 User Manual Page 91

  • Download
  • Add to my manuals
  • Print
  • Page
    / 702
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 90
2. Programming Concepts
Adjustment on Input Terminal Response Time
Function Group
D1020
Number
Contents:
1. D1020 can be used for setting up the response time of receiving pulses at X0 ~X7 for ES2
series MPU. Default: 10ms, 0~20ms adjustable.
2. When the power of PLC goes from “OFF” to “ON”, the content of D1020 is set to 10
automatically.
X0
X7
0ms
1ms
10ms
15ms
0
1
10
15
Terminal
response time
Status
memory
Update input
status
Set by D1020
(default: 10)
3. If the following programs are executed, the response time of X0 ~ X7 will be set to 0ms.
However, the fastest response time of input terminals will be 50μs due to that all terminals are
connected with RC filters..
M1000
MOV K0 D1020
normally ON contact
4. It is not necessary to adjust response time when using high-speed counters or interrupts
5. Using API 51 REFF instruction has the same effect as modifying D1020.
X6 pulse width detecting function
Function Group
M1083,M1084, D1023
Number
Contents:
When M1084 = ON, X6 pulse width detecting function is enabled and the detected pulse width is
stored in D1023 (unit: 0.1ms)
M1083 Ondetecting width of negative half cycle (OFFÆON)
M1083 Offdetecting width of positive half cycle (ONÆOFF)
2-59
Page view 90
1 2 ... 86 87 88 89 90 91 92 93 94 95 96 ... 701 702

Comments to this Manuals

No comments