Delta A Series User Manual Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 13
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
9
1030H Start pattern number 0 ~ 7
1040H~
1047H
Actual step number setting inside the
correspond pattern
0 ~ 7 = N, indicate that this pattern is executed from step 0 to step N
1050H~
1057H
Cycle number for repeating the
execution of the correspond pattern
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
1060H~
1067H
Link pattern number setting of the
correspond pattern
0 ~ 8, 8 indicates the program end. 0~7 indicates the next execution pattern number after executing
the current pattern
2000H~
203FH
Pattern 0~7 temperature set point
setting; Pattern 0 temperature is set to
2000H~2007H
-999 ~ 9999
2080H~
20BFH
Pattern 0~7 execution time setting
Pattern 0 time is set to 2080H~2087H
Time 0 ~ 900 (1 minute per scale)
6. Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data = FF00H for bit set, 0000H for bit clear)
0810H Communication write-in selection Communication write in disabled: 0 (default), Communication write in enabled: 1
0811H Temperature unit display selection
o
C / linear input (default) : 1 ,
o
F : 0
0812H Decimal point position selection Except for the thermocouple B, S, R type, all the other thermocouple type are valid. (0 or 1)
0813H AT setting OFF: 0 (default), ON : 1
0814H Control RUN/STOP setting 0: STOP, 1 : RUN (default)
0815H
STOP setting for PID program
control
0: RUN (default), 1: STOP
0816H
Temporarily STOP for PID program
control
0: RUN (default), 1: Temporarily STOP
0817H Valve feedback setting status 0: w/o feedback (default), 1: feedback function
0818H Auto-tuning valve feedback status 0: Stop AT (default), 1: Start AT
7. Communication Transmission Format : Command Code: 02: read N bits, 05: write 1 bits, 03: read N words, 06: write 1 words