Chapter 1 Introduction extension backplanes at most. 1.3 Operation of the CPU module The CPU module is the nucleus of the AH500 system. It is respons
AH500 Quick Start The CPU module is supplied with power. The system enables the initialization. y The non-latched memory is initialized. y The use
Chapter 2 Programming Table of Contents 2.1 Preparations ...
AH500 Quick Start 2.1 Preparations 2.1.1 Hardware The hardware needed in the example is as follows. 1. Eight-slot main backplane AHBP08M1-5A x 1 POWE
Chapter 2 Programming 6. Analog input/output module (6 channels) AH06XA-5A x 1 V2V1AIR1R0V0V1V3V3R3R2V2V0ERRORRUN10V, 20mA10V,0/4~20mAFEUPV0V1I1ZPC
AH500 Quick Start 1. Insert the projection under the module into the hole in the backplane. 2. Push the module in the direction indicated by the arr
Chapter 2 Programming 2. Press the clip in the direction indicated by the arrow. z Removal 1. Pull the clip in the direction indicated by the arro
AH500 Quick Start 3. The terminal block is removed. 2.3 Wiring After the modules are installed, the wiring of the modules follows. In order for the
Chapter 2 Programming The wiring of the modules is described in detail below. (Please refer to AH500 Hardware Manual for more information.) 2.3.1 Wiri
AH500 Quick Start ①Alternating-current power supply: 100~240 V AC, and 50/60 Hz ② Circuit breaker ③ Emergency stop: The emergency stop button can be
Chapter 1 Introduction Table of Contents 1.1 Manuals...
Chapter 2 Programming 2.3.2 Wiring the Digital Input Module The input signal is the direct-current power input. Sinking and sourcing are current drivi
AH500 Quick Start 2.3.4 Wiring the Analog Input/Output Module Shielded cable*1Voltage input-10 V~+10 VShielded cable*1Current input-20 mA~+20 mAShield
Chapter 2 Programming normal phenomenon which can be ignored temporarily. 2.4 Exemplification After the hardware is installed, the wiring of the modul
AH500 Quick Start 3. A pump The pump is installed near the underground pool. However, the device to which the PLC actually connects is not the pump bu
Chapter 2 Programming Next, the environment of the project is displayed, and the project name SPW appears in the upper left corner. The operation
AH500 Quick Start 2.6 Hardware Configuration After the project is created, users can configure the hardware. Suppose the configuration is as follows.
Chapter 2 Programming Double-click the CPU module to open the PLC Parameter Setting window. Type “SPW PLC” in the Name box, and then type “The examp
AH500 Quick Start addresses to the module. The default addresses are X0.0~X0.15. They exactly meet the need, and therefore they do not need to be modi
Chapter 2 Programming Users can drag AH06XA-5A to I/O 2 and drop it. The input device range is D0~D7, and the output device range is D100~D103. (The d
AH500 Quick Start The voltages of the signals are 0 V~10 V. The conversion values are 0.0 and 10.0. Click OK. After the hardware configuration is
AH500 Quick Start 1.1 Manuals Delta Electronics, Inc. provides users with the manuals related to the AH500 series programmable logic controllers acco
Chapter 2 Programming 2.7 Creating Global Symbols In order to make the program more readable and the connection with the SCADA system more convenient,
AH500 Quick Start Users can see a new piece of data. Users can create the global symbols for the data in the table above in the same way. (For the a
Chapter 2 Programming Type “FB_SPP_Sys” in the POU Name box, and then type “Supply Water Pump Control Function” in the POU Comment box. Finally, click
AH500 Quick Start VAR_INPUT When the program is executed, the value of the external variable is brought into the internal variable. If the value of th
Chapter 2 Programming Users can begin to write the program in the function block. In order to improve the convenience of scanning the program, users a
AH500 Quick Start Click ???, and type “Pump_Remote”. When “Pump_Remote” is typed, the drop-down list appears. Users can select the item directly, or t
Chapter 2 Programming To meet the condition that there is water in the underground pool and no water in the water tower, the state of Tank_R_LSW shoul
AH500 Quick Start Click ???, and type “Pump_Out”. Users can double-click the coil marked “Pump_Out”, and the drop-down list appears. Select “Set”. P
Chapter 2 Programming To meet the condition that there is no water in the underground pool, or the condition that the pump trips, users need to click
AH500 Quick Start So far the automatic program control is complete. Please write the following program in the same way. Finally, users need to save
Chapter 1 Introduction 1.2 System Frameworks The AH500 series programmable logic controller is a medium type of programmable logic control system. Th
Chapter 2 Programming 2.9 Creating Main Programs After the function block is created, users can create the main program. Right-click in the window a
AH500 Quick Start Users can see the Prog_Main window on the main screen. The difference between the function block and the main program is that the
Chapter 2 Programming After the function block interface appears, type the identifiers as shown below. Users need to create a data block for the fun
AH500 Quick Start not only the function of checking the syntax, but also the function of compiling all programs and the contents of the function block
Chapter 2 Programming consider that the value of VAR_OUTPUT and that of VAR of in the first system does not affect those in the second system. Otherwi
AH500 Quick Start MEMO 2-34
Chapter 3 Downloading and Monitoring the Program Table of Contents 3.1 Setting COMMGR ...
AH500 Quick Start After the writing of the program is complete, users can prepare to download the program. In order to increase the functions and the
Chapter 3 Downloading and Monitoring the Program The path C:\Program Files\Delta Industrial Automation\ISPSoftx.xx\drivers\Delta_PLC_USB_Driver show
AH500 Quick Start After the software is installed, users can see the USB driver in the Device Manager window. (The COM number of the USB may vary
AH500 Quick Start The configuration is as follows. Power supply CPU module Rack 1 (eight-slot main backplane) Rack 2 (eight-slot extension backplane)
Chapter 3 Downloading and Monitoring the Program 3.1 Setting COMMGR 3.1.1 Enabling COMMGR After the software is installed, the shortcut for COMMGR aut
AH500 Quick Start 3.2 Downloading the Program After the editing above is complete, users need to download the parameters and the program to the CPU m
Chapter 3 Downloading and Monitoring the Program 3.2.2 Downloading the Hardware Configuration The hardware configuration is downloaded first. Open the
AH500 Quick Start If the CPU module which is actually connected is different from the setting in ISPsoft, the HWCNFIG window will appear. Users have t
Chapter 3 Downloading and Monitoring the Program 3.3 Monitoring and Debugging the Program 3.3.1 Monitoring the Program When the program is executed,
AH500 Quick Start After the system is tested, users have to cancel the setting so that the CPU module can return to normal. z Monitoring the devic
Chapter 3 Downloading and Monitoring the Program Type “SPP01_Table” in the Monitor Table Name box, and click OK. Users can right-click a blank area
AH500 Quick Start Click . Owing to the fact that only devices are monitored and modified, users do not need a copy of the program. If users want to
Chapter 3 Downloading and Monitoring the Program 3.3.2 Debugging the Program and the System When the system operates, an error may occur, and the erro
AH500 Quick Start in all modules. In other words, for some modules, there may be no error log in the History box. Since no error occurs, users can
Chapter 1 Introduction System framework: Rack 1~rack 8+RTU modules ...............Remote I/O7 backplanes7 backplanes Note: Users are provided with th
Chapter 3 Downloading and Monitoring the Program As the picture below shows, the power supply is abnormal, and an error occurs when the analog data is
AH500 Quick Start MEMO 3-16
AH500 Quick Start System planning 1 Control panel Concentration point Over 100 metersRack 1 (eight-slot main backplane) Master Master Slave 1 Control
Chapter 1 Introduction System planning 2 Master Slave 1 Control panel Control panel Concentration point Concentration point Over 100 metersRack 1 (eig
AH500 Quick Start System planning 3 Control Panel 設備集中區 Slave 1 Control panel 設備集中區 Slave 2 Control panel Slave 3 Control panel 設備集中區 Slave 1 Control