Chapter 3 Specifications for Products
1. Setting a PROFIBUS node address
The address knobs of AH10PFBS-5A are used for setting the node address of AH10PFBS-5A on a
PROFIBUS-DP network. There are two address knobs. They are a knob corresponding to x16
0
, and a
knob corresponding to x16
1
.
The range for one address knob is 0~F.
The range for setting the node address is described below.
Address Definition
H’1~H’7D Valid PROFIBUS address
0
x16
1
x16
H’0 or H’7E~H’FF Invalid PROFIBUS address
Example: If users need to set the node address of AH10PFBS-5A to 26 (decimal value), they have to
turn the knob corresponding to x16
1
to “1”, and the knob corresponding to x16
0
to “A”.
26 (decimal value)=1A (hexadecimal value)=1x16
1
+Ax16
0
.
Points for attention:
If users set the node address of AH10PFBS-5A when AH10PFBS-5A is not supplied with power,
they have to power AH10PFBS-5A after the node address of AH10PFBS-5A is set.
If users change the node address of AH10PFBS-5A when AH10PFBS-5A is powered, the change
will not take effect immediately after the node address of AH10PFBS-5A is changed, and it will
take effect after the users cut off the power supplied to AH10PFBS-5A and then power
AH10PFBS-5A again.
To prevent the address knobs on AH10PFBS-5A from being scratched, please carefully use a
slotted screwdriver to rotate the address knobs on AH10PFBS-5A.
2. Definitions of the pins in the PROFIBUS-DP port
Pin PIN name Description
1 -- N/C
2 -- N/C
3 RxD/TxD-P Sending/receiving data (P (B))
4 -- N/C
5 DGND Data reference potential (C)
6 VP Supplying positive voltage
7 -- N/C
8 RxD/TxD-N Sending/receiving data (N (A))
N/C
1
5
9
6
9 --
3-62