Chapter 4 Assigning Addresses
User-defined input/output device range: X10.0~X10.15, and Y20.0~Y20.15
4.3.2 Start Addresses for Analog Input/Output Modules
Users can assign input registers and output registers to an analog input/output module through HWCONFIG in
ISPSoft. The input registers and the output registers should be in the range of D0 to D65535. Take AH06XA-5A
for instance. The original input registers are D0~D7, and the original output registers are D8~D11. Users can
change the input device range from D0~D7 to D50~D57, and change the output device range from D8~D11 to
D100~D103.
Default input/output device range: D0~D7, and D8~D11
User-defined input/output device range: D50~D57, and D100~D103
4-7