Chapter 5 Wiring
5-48
5.6.5 Wiring AH08DA-5B
AC motor drive,
recorder,
proportioning valve...
AC motor drive,
recorder,
proportioning valve...
converter
Shielded cable*1
Voltage output
-10 V~+10 V
Shielded cable*1
Voltage output
-10 V~+10 V
VO0
AG
CH0
*2
CH0
AG
ZP
UP
DC24V
DC/DC
+15V
-15V
AG
SG
VO7
AG
CH7
*2
CH7
AG
*4
*3
*3
SG
SG
*1. Please isolate the analog output signal cable from other power cables.
*2. If a ripple is large for the input terminal of the load and results in the noise interference with the wiring,
please connect the module to the capacitor having a capacitance in the range of 0.1 μF to 0.47 μF with a
working voltage of 25 V.
*3. Please connect the shielded cable to the terminal SG.
*4. Once AH08DA-5B is installed on a backplane, the terminal SG on AH08DA-5B and the terminal
on the
backplane will be short-circuited. Please connect the terminal
on the backplane to the ground terminal
.