Chapter 5 Wiring
5-50
5.6.7 Wiring AH06XA-5A
Shielded cable*1
V0+
I0+
VI0-
CH0
V1+
I1+
VI1-
CH1
*3
*2
CH0
1M
CH1
AG
1M
1M
AG
1M
250
250
VO1
IO1
AG
CH1
Currentoutput
0mA~20mA
CH1
AG
VO0
IO0
AG
CH0
Shielded cable*4
Voltage output
-10V~+10V
*5
CH0
AG
ZP
UP
DC24V
DC/DC
converter
+15V
-15V
AG
SG
*6
*7
*6
*6
*6
SG
SG
SG
SG
AC motor drive,
recorder,
proportioning valve…
AC motor drive,
recorder,
proportioning valve…
V2+
I2+
VI2-
CH2
*2
CH2
1M
AG
1M
250
*6
SG
Voltageinput
-10V~+10V
4mA~20mA
+
-
Current input
-20mA~+20mA
+
-
+
-
4-wire
2-wire
+24V
0V
+24V
0V
Shieldedcable*1
Current input
Shielded cable*1
Shielded cable*4
*1. Please isolate the analog input signal cable from other power cables.
*2. If the module is connected to a current signal, the terminals V1+ and I1+ must be short-circuited, and the
terminals V2+ and I2+ must be short-circuited.
*3. If the ripple in the input voltage results in the noise interference with the wiring, please connect the module
to the capacitor having a capacitance in the range of 0.1 μF to 0.47 μF with a working voltage of 25 V.
*4. Please isolate the analog output signal cable from other power cables.
*5. If a ripple is large for the input terminal of the load and results in the noise interference with the wiring,
please connect the module to the capacitor having a capacitance in the range of 0.1 μF to 0.47 μF with a
working voltage of 25 V.
*6. Please connect the shielded cables to the terminal SG.
*7. Once AH06XA-5A is installed on a backplane, the terminal SG on AH06XA-5A and the terminal
on the
backplane will be short-circuited. Please connect the terminal
on the backplane to the ground terminal
.
Page view 207