AH500 Hardware Manual
5-53
5.7.3 Wiring AH04TC-5A
I0+
I0-
FG
CH0
+
-
Shielded cable *1
Thermocouple
-150mV~150mV
I3+
I3-
FG
CH3
Cold-conjunction
compensation
INA
ADC
+
-
*1. The cable connected to the input terminal should be the cable or the shielded twisted pair cable which can
be connected to a type J, type K, type R, type S, type T, type E, or type N thermocouple, and should be kept
separate from other power cables and cables which generate noise.
5.7.4 Wiring AH08TC-5A
I0+
I0-
FG
CH0
+
-
-150mV~150mV
I7+
I7-
FG
CH7
INA
ADC
+
-
Shielded cable *1
Thermocouple
Cold-conjunction
compensation
*1. The cable connected to the input terminal should be the cable or the shielded twisted pair cable which can
be connected to type J, type K, type R, type S, type T, type E, or type N thermocouple, and should be kept
separate from other power cables and cables which generate noise.
5.8 Wiring Network Modules
5.8.1 Wiring AH10DNET-5A
5.8.1.1 DeviceNet Connector
Pin Signal Color Description
5 V+ Red 24 V DC
4 CAN_H White Signal (positive pole)
3 SHIELD -
It is connected to a
shielded cable.
2 CAN_L Blue Signal (negative pole)
1 V- Black 0 V DC