Chapter 5 Wiring
5-54
5.8.1.2 Connecting a Cable to the DeviceNet Connector
Remove the 30 millimeter plastic jacket of a
cable with a professional tool. Please do not
damage the shielded cable when the plastic
jacket is removed.
A
pproximately
30
m
m
After users remove the metallic shield and the
foil, they can see two power cables (in red and
black respectively), two signal cables (in blue
and white respectively), and one shielded
cable.
Shielded cabl
e
After the metallic shield and the foil are
removed, the users need to remove the plastic
jackets of the power cables and the plastic
jackets of the signal cables properly.
Insert the communication cable into the holes
in the connector.
Blue (CAN_L)
Shielded cable (CAN_SHLD)
Black (V-)
Red (V+)
White
(
CAN_H
)
After the communication cable is inserted into
the holes in the connector, tighten the screws
on the connector with a slotted screwdriver.
5.8.1.3 Installing the DeviceNet Connector
After the wiring is complete, users can insert the DeviceNet connector into the interface.
Tighten the two screws on the DeviceNet connector.
Points for attention:
After the communication cable is kept separate from the power cable, the electromagnetic interference is
reduced.
Only after the both ends of the shielded cable are grounded can the shielded cable be brought into full