Chapter 9 Troubleshooting
9-5
Error
code
Description Remedy
16#0063
An error occurs when the data is
written into the memory card.
(SM453)
Check whether the file path is correct, or whether the
memory card breaks down.
16#0064
The file in the memory card can
not be read. (SM453)
Check whether the file path is correct, or whether the file
is damaged.
16#0065
The file in the memory card is a
read-only file. (SM453)
Users need to set the file so that the file is not a read-only
file.
16#0066
An error occurs when the system
is backed up.
1. Check whether the memory card is normal, and
whether the capacity of the memory card is large
enough.
2. Retry the backup procedure. If the error still occurs,
please contact the factory.
16#2000
There is no END in the program
in the PLC. (SM5)
1. Compile the program again, and download the
program again.
2. Reinstall ISPSoft, compile the program again, and
download the program again.
16#2002
GOEND is used incorrectly.
(SM5)
Check the program, compile the program again, and
download the program again.
16#2003
The devices used in the program
exceed the range. (SM0/SM5)
Check the program, compile the program again, and
download the program again.
16#2004
The part of the program specified
by the label used in CJ/JMP is
incorrect, or the label is used
repeatedly. (SM0/SM5)
Check the program, compile the program again, and
download the program again.
16#2005
The N value used in MC is not
the same as the corresponding N
value used in MCR, or the
number of N values used in MC
is not the same as the number of
N values used in MCR. (SM5)
Check the program, compile the program again, and
download the program again.
16#2006
The N values used in MC do not
start from 0, or the N values used
in MC are not continuous. (SM5)
Check the program, compile the program again, and
download the program again.
16#2007
The operands used in ZRST are
not used properly. (SM5)
Check the program, compile the program again, and
download the program again.
16#200A Invalid instruction (SM5)
Check the program, compile the program again, and
download the program again.
16#200B
The operand n or the other
constant operands exceed the
range. (SM0/SM5)
Check the program, compile the program again, and
download the program again.
16#200C
The operands overlap.
(SM0/SM5)
Check the program, compile the program again, and
download the program again.
16#200D
An error occurs when the binary
number is converted into the
binary-coded decimal number.
(SM0/SM5)
Check the program, compile the program again, and
download the program again.
16#200E
The string does not end with
0x00. (SM0/SM5)
Check the program, compile the program again, and
download the program again.
16#200F
The instruction does not support
the modification by an index
register. (SM5)
Check the program, compile the program again, and
download the program again.