AH500 Hardware Manual
9-24
Error
code
Description Remedy
16#A805
The signal received by channel 5
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 5 exceeds
the range of inputs which can be received by the
hardware.
16#A806
The signal received by channel 6
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 6 exceeds
the range of inputs which can be received by the
hardware.
16#A807
The signal received by channel 7
exceeds the range of inputs
which can be received by the
hardware. (The ERROR LED
indicator is OFF.)
Check the module parameter in HWCONFIG.
Check whether the signal received by channel 7 exceeds
the range of inputs which can be received by the
hardware.
9.2.2
Troubleshooting for AH02HC-5A/AH04HC-5A
Error
code
Description Remedy
16#A001
The linear accumulation in
channel 1 exceeds the range.
To clear the linear accumulation, users need to set bit 1 in
CR0 to ON by means of FROM/TO.
16#A002
The prescale value for channel 1
exceeds the range.
Check the module parameter in HWCONFIG.
The prescale value for channel 1 should be within the
range between 0 and 32767.
16#A003
The moving average for channel
1 exceeds the range.
Check the module parameter in HWCONFIG.
The moving average for channel 1 should be within the
range between 2 and 60.
16#A004
The comparison value for
channel 1 exceeds the range.
Check the module parameter in HWCONFIG.
The comparison value for channel 1 should be within the
range between -999999999 and 999999999.
16#A005
The limit value of the alarm output
for channel 1 is incorrect.
Check the module parameter in HWCONFIG.
The limit value of the alarm output for channel 1 should
be within the range between -200000 and 200000.
16#A006
The interrupt number for channel
1 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number for channel 1 should be within the
range between 0 and 31.
16#A011
The linear accumulation in
channel 2 exceeds the range.
To clear the linear accumulation, users need to set bit 1 in
CR28 to ON by means of FROM/TO.
16#A012
The prescale value for channel 2
exceeds the range.
Check the module parameter in HWCONFIG.
The prescale value for channel 2 should be within the
range between 0 and 32767.
16#A013
The moving average for channel
2 exceeds the range.
Check the module parameter in HWCONFIG.
The moving average for channel 2 should be within the
range between 2 and 60.
16#A014
The comparison value for
channel 2 exceeds the range.
Check the module parameter in HWCONFIG.
The comparison value for channel 2 should be within the
range between -999999999 and 999999999.
16#A015
The limit value of the alarm output
for channel 2 is incorrect.
Check the module parameter in HWCONFIG.
The limit value of the alarm output for channel 2 should
be within the range between -200000 and 200000.
16#A016
The interrupt number for channel
2 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number for channel 2 should be within the
range between 0 and 31.