Delta AH500 series Manual Page 292

  • Download
  • Add to my manuals
  • Print
  • Page
    / 297
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 291
AH500 Hardware Manual
9-28
Error
code
Description Remedy
16#A01A
Incorrect division operation (The
divisor is 0.)
Modify the operation to prevent the divisor from being
zero.
16#A01B General program error Modify the program to make the syntax correct.
16#A01C
LD/LDI has been used more than
nine times.
Modify the program to prevent LD/LDI from being used
more than nine times.
16#A01D
There is more than one level of
nested program structure supported
by RPT/RPE.
Modify the program to prevent more than one level of
nested program structure supported by RPT/RPE from
being used.
16#A01E
SRET is used between RPT and
RPE.
Modify the program to prevent SRET from being used
between RPT and RPE.
16#A01F
There is no M102 in the main
program, or there is no M2 in the
motion program.
Modify the program so that there is M102 in the main
program, or modify the program so that there is M2 in
the motion program.
16#A020
The wrong instruction is used, or the
device used exceeds the range.
Check and modify the program to prevent the wrong
instruction from being used, or check whether the
device used exceeds the device range.
9.2.5
Troubleshooting for AH10EN-5A
Error
code
Description Remedy
16#A001
The IP address of host 1 conflicts
with another system on the
network.
1. Contact the network administrator, and check whether
the IP address is correct.
2. Check the module parameter in HWCONFIG.
16#A002
The IP address of host 2 conflicts
with another system on the
network.
1. Contact the network administrator, and check whether
the IP address is correct.
2. Check the module parameter in HWCONFIG.
16#A003 DHCP for host 1 fails. Please contact the network administrator
16#A004 DHCP for host 2 fails. Please contact the network administrator
16#A401 Hardware error
Please restore the hardware to the factory setting. If the
error still occurs, please contact the factory.
16#A402
The initialization of the system
fails.
Please restore the system to the factory setting. If the
error still occurs, please contact the factory.
9.2.6
Troubleshooting for AH10SCM-5A
Error
code
Description Remedy
16#A002
The setting of the UD Link is
incorrect, or the communication
fails.
Check the setting in SCMSoft, and download the setting
again.
16#A401 Hardware error Please contact the factory.
16#A804
The communication through the
communication port is incorrect.
1. Check whether the communication cable is connected
well.
2. Check the parameter in HWCONFIG, and the
parameter. Download the parameter again.
16#A808 Modbus communication error
1. Check whether the communication cable is connected
well.
2. Check the parameter in HWCONFIG, and the
parameter. Download the parameter again.
Page view 291

Comments to this Manuals

No comments