3.4 Specifications for the Power Supply Module
3.4.1 General Specifications
AHPS05-5A
Item Specifications
Supply voltage
100~240 V AC (-15%~10%)
50/60 Hz5%
Action
specifications
If the input power supply is larger than 85 V AC, the power supply module can
function normally.
Allowable
instantaneous
power failure time
If the instantaneous power failure time is within ten milliseconds, the power
supply module keeps running.
Fuse 4 A/250 V AC
Inrush current 45 A within 1 millisecond at 115 V AC
24 V DC output
The maximum current is 2.5 A.
It is only for a backplane.
Power protection
The 24 V DC output is equipped with the short circuit protection and the
overcurrent protection.
Surge voltage
withstand level
1,500 V AC (Primary-secondary), 1,500 V AC (Primary-PE), 500 V AC
(Secondary-PE)
Insulation voltage
Above 5 M
(The voltage between all inputs/outputs and the ground is 500 V DC.)
Ground
The diameter of the ground should not be less than the diameters of the cables
connected to the terminals L and N.
AHPS15-5A
Item Specifications
Supply voltage 24 V DC (-35%, +30%)
Allowable
instantaneous
power failure time
10 milliseconds
Fuse 6.3 A/250 V AC
Inrush current 30 A within 100 milliseconds
24 V DC output 1.5 A
Maximum output
power
36 W
Power protection
The 24 V DC output is equipped with the short circuit protection, the overcurrent
protection, and the overvoltage protection.
Surge voltage
withstand level
500 V AC
Ground The diameter of the ground should be greater than 1.6 mm
2
.