Doc. Name:
Setting MODBUS RS-485 communication for Delta products
Rev.: 00
Doc. Code:
134A-P-D1410-APN002-EN
Page 1/11
Topic: Setting MODBUS RS-485 Communication for Detla Products
Applicable model
AH500 series, DOP series, DVP series, IFD9506, RTU-EN01, TP series, AFE2000 series,
APF2000 series, ASDA-A series, ASDA-B series, ASDA-AB, ASDA-S series, DMV series, CTA
series, DT3 series, DTA series, DTB series, DTC series, DTE series, DTV series, DVW series,
HES series, HMC series, IED series, REG2000 series, VFD series
Keyword MODBUS RS-485, communication timeout, delay time
1. Description
The application note provides the information about setting a RS-485 communication timeout and a RS-485 delay time
for a Delta industrial automatic product for users. In order to increase communication efficiency, and shorten the time for
adjustment, the users can set a RS-485 communication timeout and a RS-485 delay time according to Table 1.
2. Setting the MODBUS RS-485 Parameters in a Delta Industrial
Product
When a MODBUS master station is connected to slave stations, the MODBUS master station sends commands to the
slave stations. The slave stations rely according to the commands they receive. Owing to the fact that there are
difference in response time and character, communication errors may occur. To meet the time that each slave station
needs, the communication timeouot and the delay time in the master station can be adjusted. If the time that the slave
station need is different, the communicaiton timeout and the delay time in the master station will be the maximum
communication timeout and the maximum delay among the slave stations.
2.1 Setting MODBUS RS-485 Parameters
This section provides the information about setting a communication timeout and a delay time for the Delta MODBUS
master station which is connected to slave stations. Please refer to Table 1 for more information.
Table 1 Table of communication timeouts and delay times
Setting a communication timeout and delay for a master station (ms)
AH500 series DVP series DOP series IFD9506/7 RTU-EN01
Timeout *Delay Timeout *Delay Timeout Delay Timeout Delay Timeout Delay
AH500 > ST 1 > ST 1 >ST 1 > ST 1 > ST 1
AFE2000 15 20 15 20 15 20 15 20 15 20
APF2000 15 20 15 20 15 20 15 20 15 20
ASD-A2R 5 4 5 4 5 4 5 4 5 4
ASDA-A 5 4 5 4 5 4 5 4 5 4
ASDA-A+ 5 4 5 4 5 4 5 4 5 4
ASDA-A2 5 4 5 4 5 4 5 4 5 4
ASDA-AB 5 4 5 4 5 4 5 4 5 4
ASDA-B 5 4 5 4 5 4 5 4 5 4
ASDA-B2 5 4 5 4 5 4 5 4 5 4
ASDA-M 5 4 5 4 5 4 5 4 5 4
ASD-S 5 4 5 4 5 4 5 4 5 4
CTA 305 20 305 20 305 20 305 20 305 20
DMV1000 2005 1 2005 1 2005 1 2005 1 2005 1
DMV2000 10 1 10 1 10 1 10 1 10 1
Slave station
DOP-B 30 50 30 50 30 50 30 50 30 50
s
DPM-C530 1175 2000 1175 2000 1175 2000 1175 2000 1175 2000
Page view 0
1 2 3 4 5 6 ... 10 11

Summary of Contents

Page 1 - Product

Doc. Name: Setting MODBUS RS-485 communication for Delta products Rev.: 00Doc. Code: 13

Page 2

Doc. Name: Setting MODBUS RS-485 communication for Delta products Rev.: 00Doc. Code: 13

Page 3

Doc. Name: Setting MODBUS RS-485 communication for Delta products Rev.: 00Doc. Code: 13

Page 4 - 3.1 AH500 Series

Doc. Name: Setting MODBUS RS-485 communication for Delta products Rev.: 00Doc. Code: 13

Page 5

Doc. Name: Setting MODBUS RS-485 communication for Delta products Rev.: 00Doc. Code: 13

Page 6

Doc. Name: Setting MODBUS RS-485 communication for Delta products Rev.: 00Doc. Code: 13

Page 7 - 3.2 DVP Series

Doc. Name: Setting MODBUS RS-485 communication for Delta products Rev.: 00Doc. Code: 13

Page 8 - 3.3 DOP Series

Doc. Name: Setting MODBUS RS-485 communication for Delta products Rev.: 00Doc. Code: 13

Page 9 - 3.4 IFD Series

Doc. Name: Setting MODBUS RS-485 communication for Delta products Rev.: 00Doc. Code: 13

Page 10 - 3.5 RTU Series

Doc. Name: Setting MODBUS RS-485 communication for Delta products Rev.: 00Doc. Code: 13

Page 11

Doc. Name: Setting MODBUS RS-485 communication for Delta products Rev.: 00Doc. Code: 13

Comments to this Manuals

No comments