Delta RMC101 User Manual Page 293

  • Download
  • Add to my manuals
  • Print
  • Page
    / 951
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 292
Digital I/O 5.1
Communications 5-43
(including Actual
Position, Actual Speed,
Drive, Error Bits, and
other Status Bits)
one axis per command
cycle
Input to
Event Mode
Does not require a PLC
Multiple axes may be
given commands from a
single input
Allows use of Event
Control feature
Returns only a Halted
Bitindicating an error
has occurred
and an In
Position Bit per axis
Issues only Start Event
commands
Implementation
The following diagram shows the electrical control connections of a single-axis hydraulic system
using RMC-DI/O in Parallel Event Mode (the PC and its RS232 cable are needed only during
setup):
This document discusses only the connections between the Programmable Controller and the
RMC. For details on the transducer and drive wiring, look up Wiring Notes in the RMCWin index.
The following points describe the operation of Parallel Event mode:
Parallel Event mode uses the following digital inputs and outputs. The following table is intended
to match input and output number with the names associated with each. Their uses will be
described below.
CPU DI/O:
Input 0
Run/Stop
Input 1
Unused
Output 0
Ready
Output 1
Acknowledge
Communication DI/O:
Inputs 0-7
Axis 0 Event Step