Delta RMC101 User Manual Page 324

  • Download
  • Add to my manuals
  • Print
  • Page
    / 951
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 323
RMC100 and RMCWin User Manual
5-74
Nf:r + 4 Step n (0-255) Command Value
Nf:r + 5 Step n (0-255) Command/Commanded Axes
Nf:r + 6 Step n (0-255) Link Type/Link Next
Nf:r + 7 Step n (0-255) Link Value
Input to Event Table Registers:
These registers can be read or written.
Allen-
Bradley
and SoftPLC
Register Description
N17:0
Event Step for Axis 0 on Input 0 Rising Edge
N17:1
Event Step for Axis 1 on Input 0 Rising Edge
N17:2
Event Step for Axis 2 on Input 0 Rising Edge
N17:3
Event Step for Axis 3 on Input 0 Rising Edge
N17:4
Event Step for Axis 4 on Input 0 Rising Edge
N17:5
Event Step for Axis 5 on Input 0 Rising Edge
N17:6
Event Step for Axis 6 on Input 0 Rising Edge
N17:7
Event Step for Axis 7 on Input 0 Rising Edge
N17:8 + n
Event Step for Axes n (0-7) on Input 1 Rising
Edge
:
N17:120 + n
Event Step for Axes n (0-7) on Input 15
Rising Edge
N17:128 + n
Event Step for Axes n (0-7) on Input 0 Falling
Edge
:
N17:248 + n
Event Step for Axes n (0-7) on Input 15
Falling Edge
Status Map Registers:
This block of registers is only used by the Modbus Plus and PROFIBUS interfaces. Therefore,
these registers are unused by this Ethernet protocol.
Page view 323
1 2 ... 319 320 321 322 323 324 325 326 327 328 329 ... 950 951

Comments to this Manuals