The controlling connection is broken due to a timeout. This will occur when the cable is
disconnected, when excessive collisions cause the connection to timeout, or when the client is
powered off or reset.
The controlling client intentionally closes the connection. This can happen when an I/O
connection is removed, when a new program is downloaded to the client, or when the connection
is reconfigured to have a different RPI or data size.
Although not strictly a broken connection, the condition of the controlling client switching from
Run to Program mode also triggers this handling.
Note: All of these conditions only apply to the controlling client and its connection. No broken
connection actions will be done when an Input Only connection is broken.
The action taken when any of these conditions occur is selectable by the Broken Connection
Action byte of the Configuration Data described in Controlling the RMC over EtherNet/IP I/O. If
this byte is omitted, the connection will behave as though the Broken Connection Action byte was
specified as -1. The following values define the recovery action taken:
Value
Action
-1
Every axis without the Continue bit set in its Configuration word is
halted and its event step sequence stops if it was running. All such
axes will receive the Halt (H) command unless they are in open loop, in
which case they will receive the Disable Drive Output (K) command.
For more flexibility, use Broken Connection Action values of 0 to 31 as
described below.
0 to
15
The Simulate Rising Edge ({ ) command is issued to axis 0 with a
command value equal to the value of the Broken Connection Action
byte (0 to 15). This allows the user to define an event sequence to run
on any or all of the axes. Therefore, event sequences can be stopped
and other special recovery sequences can be run. Review the Simulate
Rising Edge command and the Input-to-Event table for details.
16 to
31
Same as 0 to 15, except that the Simulate Falling Edge (}) command is
issued with a command value equal to the value of the Broken
Connection Action byte minus sixteen (0 to 15).
Handling Broken I/O Connections in the ControlLogix
The ControlLogix has two methods of handling a broken connection with an EtherNet/IP device
such as the RMC:
In the Module Properties dialog box for the RMC, on the Connection tab, the Major Fault On
Controller If Connection Fails In Run Mode check box can be checked to fault the ControlLogix
when the EtherNet/IP connection to the RMC is broken.
The Get System Value (GSV) block can be used to read the status of the connection in ladder
logic. The following ladder logic demonstrates this: