RMC100 and RMCWin User Manual
5-206
The MSTR block indicates it will do an operation using the control block beginning at 400130,
using the one register at 400200. When this block is finished, we look at the third least significant
bit, which represents node 3. If this bit is cleared, then the RMC is disconnected.
The next step is to set up the control block:
Register
Content
400130
9 (decimal): Operation type: Peer Cop Health
400131
0000 (hex): Error status: filled in by function
400132
1 (decimal): Length: we only want one register
400133
0 (decimal): Word Index: we want the first word in
the table
400134-8
0 (decimal): Unused
5.3.7.6 MSTR Block Error Codes
The following list of error codes are returned by the MSTR function block:
Error Code
(Hex)
Meaning
1001
User-initiated abort
2001
Invalid operation type
2002
User parameter changed
2003
Invalid length
2004
Invalid offset
2005
Invalid length + offset