Delta RMC101 User Manual Page 464

  • Download
  • Add to my manuals
  • Print
  • Page
    / 951
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 463
RMC100 and RMCWin User Manual
5-214
Right-click on the RMC slave device icon, and select Configure from the shortcut menu.
Move the cursor to the top row’s I Addr cell, and either enter the offset that you wish to access
the data at, or click the Auto Addr. button. Do the same for the O Addr cell.
Click OK.
7. Add any other RMC devices you want on the same network. To do this, repeat steps 5 and 6.
8. Save your configuration.
9. Send the configuration to the master device. This step varies greatly depending on the type of
master you use.
5.4.4 Configuring a PROFIBUS-DP Network with SST Profibus
Configuration
Before reading this topic, you should read and understand PROFIBUS Configuration. This topic
only gives a specific example of doing one step of the configuration process. In addition, SST
may, and probably will, change the steps taken here slightly with each version of SST Profibus
Configuration.
The following steps have been tested with SST Profibus Configuration versions 1.2 and 1.4:
1. Start SST Profibus Configuration.
2. If you are modifying an existing PROFIBUS-DP network, open your current configuration file.
3. If you are creating a new PROFIBUS-DP network, you must create a new network and add a
master device to the network:
On the File menu, click New.
The tree-type control on the left is the GSD library. It contains all devices known about. In this
tree, expand Masters and SST and double-click on the SST master you will be using (e.g. SST-
PFB-SLC).
In the Station box, enter the station address of your master. Click OK.
On the Online menu, click Network Properties.
In the Baud Rate field, select your desired baud rate. The RMC is capable of speeds up to
12000kBaud (12MBps); check the rates supported by your master and other slave devices.
Click OK.
4. Add the DELT1630.GSD file to your configuration program’s GSD database.
This step may not be necessary. SST ships a GSD file for the RMC. However, as of this writing it
shipped revision level 1.1 of the GSD file. Revision 1.2 or newer is required for using Message
Mode, and Rev 1.3 is required for Compact Mode without Sync. To check the revision level, do the
following:
In the GSD library tree, expand Slaves and Delta Computer Systems, Inc. and right-click on the
Page view 463
1 2 ... 459 460 461 462 463 464 465 466 467 468 469 ... 950 951

Comments to this Manuals

No comments