9 Fault 1 - Bit
S
1 Fault 1 - Bit H
8
Fault 0 - Bit
S
0
Fault 0 - Bit H
For each fault, the two bits in the Auto Stop parameter define the action as follows:
Bit
H
Bit
S
Description
0
0
Status Only
0
1
Soft Stop
1
0
Hard Stop
1
1
Disable Drive
If you select Status Only for a fault that cannot use that action, then the axis will use a Soft Stop
action for that fault. Similarly, if you select Disable Drive for a fault on an axis that does not have
an Amp Enable output, the axis will use the Hard Stop action for the fault.
C.6.15 Auto Stop Bit Map