Delta RMC101 User Manual Page 903

  • Download
  • Add to my manuals
  • Print
  • Page
    / 951
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 902
Appendix E: Event Step Link Reference
E-13
Example 2:
Link Type: InputLow (o)
Link Value: 0
Link Next: 15
This link waits until input bit 0 of the Communication DI/O (or CPU if no Communication DI/O is
present) is OFF before going to step 15.
E.4.7 Link Type - Jump Using Inputs
Link
Type:
Jump (J, hex 0x4A, dec 74)
Link
Value:
Link Value: Reserved must be 0
Range:
Reserved must be 0
Note: This feature is available only in RMC100 CPU firmware version 19990625 and later.
Note: This link type cannot be used with the Poll (?) command.
This link type is unique in that both the Link Value and Link Next fields are ignored. When this link
type is encountered two discrete inputs are used to determine which event step is jumped to. This
link is taken immediately; no condition is waited for.
The inputs used depend on the RMC hardware available. If there is a Sensor DI/O, its inputs 16
and 17 are used. If there is no Sensor DI/O, but there is a Communication DI/O, its inputs 16 and
17 are used. If there is no DI/O module, then CPU inputs 0 and 1 are used.
This chart shows how the input levels determine the next event step:
Input
17
or
1
16
or 0
Next Event Step
0
0
Current Event Step +
1
0 1
Current Event Step +
2
1
0
Current Event Step +
3
Page view 902
1 2 ... 898 899 900 901 902 903 904 905 906 907 908 ... 950 951

Comments to this Manuals

No comments