RMC100 and RMCWin User Manual
F-2
mA
8 axes (6 slots)
Typical 585 mA @ 24 VDC, max 750
mA
DC-DC converter
isolation
500 VAC, 700 VDC, input to controller
Mechanical
Dimensions - 2 axes (3
slots)
4.12 x 5.95 x 4.75 in
(10.5 x 15.0 x 12.1 cm) (WxHxD)
8 axes (6 slots)
7.12 x 5.95 x 4.75 in
(18.1 x 15.0 x 12.1 cm) (WxHxD)
Weight - 2 axes (3 slots)
2.0 lb (0.9 kg) max
8 axes (6 slots)
3.0 lb (1.4 kg) max
Mounting
Options
Symmetrical DIN 3 or panel-mount
Orientation
The RMC should be mounted upright on
a vertical surface, such that the air holes
are on top and bottom.
Clearance, above and
below
The amount of clearance required
depends on the maximum ambient
temperature:
Above 122°F (50°C) 3 in (7.6 cm)
86 to 122°F (30 to 50°C) 2 in (5.1 cm)
Less than 86°F (30°C) 1 in (2.5 cm)
Environment
Operating temperature
+32 to +140°F (0 to +60°C)
Storage temperature
-40 to +185°F (-40 to +85°C)
Humidity
93%, non-condensing
Compliance
CE, UL, Canadian UL (see details
below)
Agency Compliance
Page view 925