Appendix B: Tuning RMC100 Startup Guide
52
deltamotion.com
Double-click the Config Word (in the parameter area of the main
screen) for the pressure axis.
In the Input type field, select the type of feedback of your pressure
transducer.
iii. Set scale and offset
On the Tools menu, click Scale/Offset Calibration.
If the axis is pressure control:
Enter the desired Actual Pressure for two different pressure counts
(the counts are the feedback from the transducer). The scale and
offset will be automatically calculated.
If the axis is force (differential pressure) control:
Enter the following information:
Maximum gauge reading
Actuator Type
Cylinder Dimensions
Desired Force Units
Desired Force Direction
This information allows the Actual Pressure in the Status area of
the main screen to display the net force on the cylinder.
Click Apply or Done when you are finished.
2. Assign the Pressure Axis to a Position Axis
The RMC performs pressure control using two or more inputs from transducers
and one drive output to the hydraulic valve. Any position axis with analog
drive output (not stepper output) can be used to provide the drive output and
position input. To enable pressure control on this position axis, you must
assign a pressure-enabled analog axis to the position axis. In this configuration,
the analog inputswhether using two transducers monitoring differential force,
or a single transducer monitoring single-ended pressureare then used together
with the position axis to control both position and pressure.
To assign a pressure axis to a position axis:
a) Double-click the Config Word for the position axis. This will open
the Config Word dialog box.
b) In the Pressure Axis field, click the desired Pressure Axis.
c) Click OK.
c) Issue a Set Parameters (P) command to cause these bits to take effect.
d) If you want the axis assignment to be remembered after the RMC
power is cycled, then issue an Update FLASH (U) command
.
This needs to be done only once.
3. Set Up the Event Step Table
Setting up and tuning position/pressure control requires issuing multiple
Page view 51