Delta PG-35 Service Manual Page 39

  • Download
  • Add to my manuals
  • Print
  • Page
    / 78
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 38
7-1
ELECTRICAL DATA
SM DELTA 1-E.2 GB
7. ELECTRICAL DATA
7.1 Single Phase Units
MODEL
Delta 22 Delta 25
Power Supply
To indoor To indoor
1PH,220-240V,50Hz 1PH,220-240V,50Hz
Max Current, A 5.2 6.3
Circuit Breaker,A 12 12
Power Supply Wiring No. X
Cross Section mm
2
3x1.0 mm
2
3x1.0 mm
2
Interconnecting Cable RC
Model No. X Cross Section mm
2
4x1.0 mm
2
4x1.0 mm
2
MODEL
Delta 35 Delta 50
Power Supply
To indoor To indoor
1PH,220-240V,50Hz 1PH,220-240V,50Hz
Max Current, A 7.5 10.3
Circuit Breaker,A 15 20
Power Supply Wiring No. X
Cross Section mm
2
3x1.5 mm
2
3x1.5 mm
2
Interconnecting Cable RC
Model No. X Cross Section mm
2
4x1.5 mm
2
5x1.5 mm
2
(a) The Inrush current is the current when power is up (charging the DC capacitors of
the outdoor unit controller).
(b) Starting current is the current when starting the compressor.
NOTE
Power wiring cord should comply with local lows and electrical regulations
requirements