11-3
CONTROL SYSTEM
SM DELTAZ 1-E.0 GB
Speed Controlled by
High Relay
Low Triac (40% to 95% effective voltage)
11.1.6.2 OFAN Operation in Cooling Mode
With keeping the OFAN general rules above in the highest priority, the operation of the OFAN will be operating
as the following:
OAT
Initial
Time After Compressor start up (minutes)
0 – 3min > 3min
OAT
Initial
>20
(or Faulty)
High(Relay)
OAT
Initial
20 Low(Triac)- Open Loop
Note:
The OAT
Initial
value represents one OAT reading exactly at the moment start up (actual freq>0).
Low (Triac)- By OMT represents the operation of the Low Fan speed controlled by Triac
according to OMT sensor.
11.1.6.3 OFAN Operation in Heating Mode
Except to the “General rules”, the outdoor fan will always be running at High speed during heating
operation mode.
11.1.7 EEV (electronic Expansion valve) Control
EEV opening is defined as EEV = EEV
OL
+ EEV
CV
EEV
OL
is the initial EEV opening as a function of the compressor frequency, operation
mode, unit model and capacity.
EEV
CV
is a correction value for the EEV opening that is based on the compressor
temperature.
During the first 5 minutes of compressor operation EEV
CV
= 0.
Once the first 5 minutes are over, the correction value is calculated as follow: EEV
CV
(n)
= EEV
CV
(n-1) + EEV
CTT
EEV
CTT
is the correction based on the compressor temperature. A target compressor
temperature is set depending on frequency and outdoor air temperature, and the actual
compressor temperature is compared to the target temperature to set the required
correction to the EEV opening.
OAT (current)
High (Relay)
18 21
Low (Triac)- By CDT
First Time enters the
default is the last state
Note : OAT faulty , use High Speed