2-1
PRODUCT DATA SHEET
SM DELTAZ 1-E.0 GB
2. PRODUCT DATA SHEET
2.1 Delta 25 / DCR 25Z R410A
Model Indoor Unit
DELTA 25 DCI
Model Outdoor Unit
DCR 25 Z R410A
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
(4)
Btu/hr 8530(4090-10240) 8530(3410-10910)
kW 2.5(1.2-3.0) 2.5(1.0-3.2)
Power input
(4)
kW 0.78 0.69
EER (Cooling) or COP(Heating)
(4)
W/W 3.21 3.61
Energy efficiency class A A
Power supply V/Ph/Hz 220-240V ~1Ph 50/60Hz
Rated current A 3.5 3.1
Starting current A 10.5
Circuit breaker rating A 10
INDOOR
Fan type & quantity Crossflow x 1
Fan speeds H/M/L RPM 1200/1050/850
Air flow
(1)
H/M/L m3/hr 420/350/270
External static pressure Min-Max Pa 0
Sound power level
(2)
H/M/L dB(A) 54/50/47
Sound pressure level
(3)
H/M/L dB(A) 39/35/32
Moisture removal l/hr 1
Condenstate drain tube I.D mm 16
Dimensions WxHxD mm 680x185x250
Weight kg 7
Package dimensions WxHxD mm 740x265x320
Packaged weight kg 10
Units per pallet units 36 units per pallet
Stacking height units 9 levels
OUTDOOR
Refrigerant control Capillary
Compressor type,model Rotary, TOSHIBA DA89X1C-20FZ3
Fan type & quantity Propeller(direct) x 1
Fan speeds H/L RPM 830
Air flow H/L m3/hr 1460
Sound power level H/L dB(A) 65
Sound pressure level
(3)
H/L dB(A) 55
Dimensions WxHxD mm 760x245x545
Weight kg 31
Package dimensions WxHxD mm 880x310x610
Packaged weight kg 33
Units per pallet Units 12 units per pallet
Stacking height units 3 levels
Refrigerant type R410A
Refrigerant chargless distance kg/m 0.85kg/7.5m
Additional charge per 1 meter g/m L10m:+0g 10<L15m:+200g
Connections between
units
Liquid line In.(mm) 1/4"(6.35)
Suction line In.(mm) 3/8"(9.53)
Max.tubing length m. Max.15
Max.height difference m. Max. 10
Operation control type Remote control
Heating elements kW
Others
(1)
Airflow in ducted units; at nominal external static pressure.
(2)
Sound power in ducted units is measured at air discharge.
(3)
Sound pressure level measured at 1-meter distance from unit.
(4)
Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).