Delta 23-730 Specifications Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 18
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
50 Hz Mini/Micro
Computer Regulator (MCR) Series
Installation and Operation Manual
Contact Technical Services at (800) 377-4384 with any questions.
Fax-on-Demand: (877) 888-9329, Document #: 8412
2
General Description and Specifications
The Sola Micro/Minicomputer regulator provides voltage regulation and
isolation from both transverse and common mode noises for any type of load.
It also suppresses transients, protects from overloads and serves as a
portable dedicated line. It is the ultimate in AC power conditioning equipment.
Two types of units are manufactured. Hardwired units, rated 125 to 1500VA,
should be permanently installed by competent electricians. Portable units,
rated 150 to 2000VA, are designed for office type environments and have a
low 43dB sound level.
Operating Temperature Range:
-20
°
C to + 50
°
C
Phase:
Single
Input Voltage (Hardwired Models):
Refer to Table 4
Input Voltage (Portable Models):
220/240 VAC
Output Voltage (Hardwired models):
110/120/220/240 VAC
Output Voltage (Portable models):
220 or 240 VAC, switch selectable*
Output Voltage Regulation:
+/-5% for an input line variation
of +/-15%.
Output Harmonic Distortion:
Less than 3% total RMS content at
full load with rated input voltage
Efficiency:
85% at full load.
Dropout:
No loss of output for line loss of
3msec.
Common Mode Noise Rejection:
Greater than 120dB
Transverse Mode Noise Rejection:
Greater than 60dB
Safety Approvals:
Designed and built per VDE 0550
and 0806. Specifications
(compatible with IEC 380/435)
* The unit must not be powered while operating this switch. Unplug the unit
from the power source before using this switch.
Page view 1
1 2 3 4 5 6 7 ... 17 18

Comments to this Manuals