Delta DT3 User Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 21
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
12
c Coef and DeadBand are added in the PID parameter for double output (one for heating and one for cooling). Coef refers to
the ratio between the first and second portions of output (P parameter of second group =Coef*P, Coef= 0.01~99.99);
DeadBand is the overlapping temperature of the P output of the first group and the second group.
¾ Set parameter
to in Initial Setting Mode
¾ To set for heating or cooling control: Select desired output control by parameter
in Initial Setting Mode. If no
board is inserted in Output2, selection items are: H1, C1 (H for heating, C for cooling, 1 for output 1). If a board is inserted in
Output 2, selection items are: H1H2, C1H2… H1A2(H for heating, C for cooling, 1 for output 1, 2 for output 2, A for Alarm 3 )
¾ Select number of PID sets as running parameter and set PID parameter: Select 0~5,
, by parameter in
Regulation Mode, then press
key to set the selected PID parameter including “SV‘x’”, ”P‘x’”, ”I‘x’”, ”d‘x’”, and ”ioF‘x’”,
where ‘x’ is the pre-selected set as the PID running parameter, which can be 0~5. “SV‘x’” is the reference temperature
setting value; “P‘x’”, ”I‘x’”, ”d‘x’”, ”ioF‘x’” correspond to P, I, D, and IOF.
¾ Set the control period: in parameterRegulation Mode, PV displays “o‘x’-‘y’”, ‘x’ is 1(output 1) or 2 (output 2), ‘y’ is H(Heating)
or C (Cooling)
¾ Set double output Coef: Set Coef value by parameter
in Regulation Mode
¾ Set DeadBand of double output: Set DeadBand zone by parameter
in Regulation Mode
¾ Set control to running mode: Set parameter
in Operation Mode to .
¾ Set AT: Set parameter
to in Regulation Mode. The selected number of PID will be adjusted
automatically. After that, a pre-set parameter of integrated PID value will be created automatically and the display will
automatically alter into
.
Note: When performing AT, the entire system must complete setting; i.e. the input Sensor must be wired and correctly set, and the
output must be connected to a heater or cooler pipe.
z MANUAL Mode: Manual control function, may force output of a fixed value; normally operated by combining switchover of PID
control.
a Switch from PID control to manual control: Control output will maintain the original control output before switching over to
manual control. E.g., if the control output before the PID calculation is 20%, then the control output after switching to manual
control is 20%. You may force a fixed output value after a switchover, for example: controlling the output to be 40%.
b Switch from manual control to PID control: if manual control before switching-over to PID control is 40%, the program will
take 40% as the initial value for calculating the PID value and output the new control.
Note: If power of machine is switched off in manual control mood, the output % will be maintained when the power is switched on
again.
¾ Set parameter
to in Initial Setting Mode
¾ Set control period: in parameter Regulation Mode, PV displays “o‘x’-‘y’”, ‘x is 1 (output 1) or 2 (output 2), ‘y’ is H (Heating)
or C (Cooling)
¾ Set output %: in parameter Operation Mode, PV screen displays “oUt‘x’”, ‘x’ is 1 (output 1) or 2 (output 2)
z FUZZY Mode: This comprises 2 parts: PID parameters and Fuzzy exclusive parameters. Since Fuzzy control is calculated based
on P.I.D values of PID control, the user must first set P.I.D parameters or perform auto tuning (AT) to produce these parameters. In
addition, Fuzzy control includes the following 2 exclusive parameters.
a Fuzzy Gain Setting: altering this value will directly affect the calculation of Fuzzy gain. Increasing this value will directly
enhance the Fuzzy control; decreasing this value will weaken the Fuzzy control. It is recommended that this value shall be
decreased for systems with slow reaction to heating/cooling. This value may be increased for systems with quick reaction to
heating/ cooling.
b Set Fuzzy DeadBand: The effective bandwidth of Fuzzy control, when PV value enters into the range of SV-FZDB
<PV<SV+FZDB, Fuzzy control will stop calculation. I.e., when the PV is within this temperature range, its Fuzzy control is
fixed.
¾ Set parameter
to in Initial Setting Mode
¾ Set Fuzzy Gain: Set value of Fuzzy Gain by parameter
in Regulation Mode.
¾ Set Fuzzy DeadBand: Set value of Fuzzy DeadBand by
parameter in Regulation Mode.
Setting of multiple PID sets
When PID control is selected, the system provides 6 sets (PID 0~5) PID parameter sets (P, I, D and IOF parameter) to be selected by the
user. In general conditions, one set of PID (P0) is adequate. For different setting values (SV), when the same PID value is not adequate
to control the precision, the user may set up multiple sets of PID parameters for the system to automatically switch-over to an applicable
PID set.
¾ Set only one PID set:
Set parameter
to 0 (PID 0, the first set) inRegulation Mode, set parameter to ON; at this time, the System starts to
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 20 21

Comments to this Manuals

No comments