Delta DT3 User Manual Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 21
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
2
V: Voltage Pulse Output, 12V ±10%
C: DC Current Output 4 ~ 20 m A
L: Linear Voltage Ouptut 0 ~ 10 VDC
EVENT inputs/ CT function (optional) 1
0: None, 1: Event Input3, 2: RS-485 Communication
EVENT inputs/ CT function (optional) 2
0: None, 1: Event Input2, 2: CT measure input2, 3: Retransmission Output
EVENT inputs/ CT function (optional) 3
0: None, 1: Event Input1, 2: CT measure input1, 3: Remote Setpoint input
Specifications
Input Voltage AC 80 ~ 260 V, 50/60Hz; DC24 VDC ±10%
Power Consumption 5VA max.
Display Method LCD display. Process value (PV): Yellow color, Set point (SV): Green color
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
3-wire Platinum RTD: Pt100, JPt100
Sensor Type
Analog input: 0 ~ 5 V, 0 ~ 10 V, 0 ~ 20 m A, 4 ~ 20 mA, 0 ~ 50 mV
Control Mode
PID, PID program control (Ramp/Soak control), FUZZY, Self-tuning, Manual and On/FF
Relay output: Max. load 250VAC, 5A resistive load
Voltage pulse output: DC 12V, Max. output current 40mA
Current output: DC 4 ~ 20m A output (Load resistance: Max. 500)
Control Output
Analog voltage output: 0 ~ 10V
Warning Output Type Relay output: Max. load 250VAC, 3A resistive load
Display Accuracy 0 or 1 digit to the right of the decimal point (selectable)
Sampling Rate Analog input: 0.1 sec/ per scan; Thermocouple or Platinum RTD: 0.1 sec/per scan
Vibration Resistance
10 to 55Hz, 10m/s
2
for 10min, each in X, Y and Z directions
Shock Resistance
Max. 300m/ s
2
, 3 times in each 3 axes, 6 directions
Ambient Temperature
0°C ~ +50°C
Storage Temperature
-20°C ~ +65°C
Altitude
Max. 2000m
Relative Humidity 35% ~ 80% RHnon-condensing
Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operation
mode. Press the
key to switch to regulation mode. If the key is pressed for more than 3 seconds, controller will switch to the
initial setting mode. Pressing the
key while in the regulation mode or initial setting mode, forces the controller to return to the
operation mode..
PV/SV: Sets the temperature set point and displays the temperature process value. Use
keys to set the temperature set
point.
Setting method: While in any function mode, press the
key to select the desired function and use keys to change
settings. Press
key to save the changes.
The flow chart below shows how to switch the settings and internal functions:
Regulation Mode Operation Mode
Initial Setting Mode
Press key les s than 3 sec
Press key
Press key more than 3 sec
Press key
Operation ModeParameter Setting:
Display
Description
Factory Setting
Use
to set temperature set point, use to switch between the display parameter
RUN/STOP: Control setting RUN or STOP
RUN
PATTERN: Start pattern setting (set control mode to PROG mode)
0
STEP: Start step setting (set control mode to PROG mode)
0
SELECT POINT: Decimal point setting (0: integral ; 1: one decimal point)
1
LOCK: Setting lock mode (LOCK1: all; LOCK2: onlySV and F1/F2 key is allowed)
OFF
ALARM1 HIGH: Upper limit alarm 1 (display according to the setting in ALARM mode)
4.0
Page view 1
1 2 3 4 5 6 7 ... 20 21

Comments to this Manuals

No comments